Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE AN APPROVED GUARD RAIL AT MAKE UP IN UNIT PER 2006 IMC PROVIDE ROOF JACKS AT WATER SUPPLY + COOLER DRAIN. OK TO TERMINATE COOLER CHAIN INTO FLOOR SINK. PROVIDE COVER OVER FAN MOTOR + BELTS IN ROOF. INSTALL EXHAUST DUCT PER DETAILS ON PLANS, BLOCKING MISSING. |
|
| 01/05/2011 | MECHANICAL - INTERMEDIATE | Approved |