Permit: T10CM00865

Parcel: 130055920


Addresses:

2585 E 36TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/02/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/27/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MET WITH CONTRACTOR TO DISCUSS EFFECTIVE GROUND PATH BONDING
08/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #5 ALL ALUMINUM RAILING FOR MODULES TO BE BONDED
08/11/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH #3, 9 & 5
06/16/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
1 - NEED TO SEE INTO METER SOCKET
2 - GROUNDING ELECTRODE CONDUCTOR INSTALLED IN RACEWAY TO BE PER SECTION 250.64 (E)
3- VERIFY #8 TO PV ARRAYS
4 - MOUNT GROUND LUG IN JUNCTION BOXES PER 250.8 & 250.12
5 - BOND FRAME FOR ARRAY MODULES