| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/02/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/27/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MET WITH CONTRACTOR TO DISCUSS EFFECTIVE GROUND PATH BONDING |
|
| 08/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #5 ALL ALUMINUM RAILING FOR MODULES TO BE BONDED |
|
| 08/11/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH #3, 9 & 5 |
|
| 06/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1 - NEED TO SEE INTO METER SOCKET 2 - GROUNDING ELECTRODE CONDUCTOR INSTALLED IN RACEWAY TO BE PER SECTION 250.64 (E) 3- VERIFY #8 TO PV ARRAYS 4 - MOUNT GROUND LUG IN JUNCTION BOXES PER 250.8 & 250.12 5 - BOND FRAME FOR ARRAY MODULES |