Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/27/2011 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INLINE EXHAUST FANS ARE TO BE HUNG WITH SPRING ISOLATORS PER PLANS 2) PROVIDE PROPER DUCT SUPPORT, DUCTS NOT TO BE SUPPORTED BY FLEX CONNECTORS 3) PROVIDE 125 PERCENT CONVERGING BRANCH TAPS (H.E.) ON ROUND DUCT TAKE-OFFS PER PLANS 4) DIFFUSER OUTLETS TO BE FRAMED ON A MINIMUM OF THREE SIDES |