Permit: T10CM00802

Parcel: 12620001C


Addresses:

3400 E ZOO CT


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM00802

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/04/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/27/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INLINE EXHAUST FANS ARE TO BE HUNG WITH SPRING ISOLATORS PER PLANS
2) PROVIDE PROPER DUCT SUPPORT, DUCTS NOT TO BE SUPPORTED BY FLEX CONNECTORS
3) PROVIDE 125 PERCENT CONVERGING BRANCH TAPS (H.E.) ON ROUND DUCT TAKE-OFFS PER PLANS
4) DIFFUSER OUTLETS TO BE FRAMED ON A MINIMUM OF THREE SIDES