Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T10CM00802
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2012 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
02/03/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
01/17/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
01/06/2012 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK DATA ROOM, RESTROOMS, KEEPERS WORK AREA AND FOOD CT. STORAGE 2) PLEASE PROVIDE AS MUCH CLEARANCE AS POSSIBLE IN FRONT OF HYDROLIC PUMP CONTROL PANEL, VFD EQUIPMENT CANNOT BE MTD OVER PUMP EQUIP. 110.26 NEC |
|
12/19/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) ELEPHANT HYDROLIC CONTROL PIPE RUN OK |
|
12/06/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/16/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
11/01/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER FROM ENGINEER OF RECORD TO AUTHORIZE USE OF EMT INSIDE BLDG FOR PV SYSTEM 2) OK TO CLEAR (COMM) TEC NEW ELEPHANT EXHIBIT SERVICE 3) CONTRACTOR TO USE LOCKOUT/TAGOUT SYSTEM. ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRICAL EQUIPMENT |
|
10/26/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) PARTIAL 1 1/4" CONDUIT FOR PV SYSTEM FROM UNDER ROOF TO INVERTER TO PANEL "B" |
|
10/18/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/30/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
09/14/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
03/25/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) UFERS REQUIRED PER 250.32, 250.104 & 250.50 APPLIES 2) CONTRACTOR TO RFI ENGINEER OF RECORD FOR POOL BONDING |