Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T10CM00802
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2012 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* 1) FENCE BARRIER CASSION FOOTINGS |
|
| 01/09/2012 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 2 FENCE BARRIER CAISSON FOOTINGS-OK TO POUR FOOTINGS |
|
| 01/05/2012 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 5 BARRIER FENCE POST FOOTINGS; DETAIL #OS-402 OK TO POUR FOOTINGS |
|
| 12/27/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 11 CASSIONS WEST 1/2 COMPLETE |
|
| 12/09/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 13 CASSION FOOTINGS AS PER DETAIL 313 CABLE BARRIER OK TO POUR PROGRESS AREAS |
|
| 12/08/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
| 12/01/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 9 DIVIDING CASSIONS AND 2 SWING GATE REBAR OK |
|
| 11/29/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) CASSIONS AT EXHIBIT DIVISION |
|
| 11/28/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* | |
| 11/22/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 6-8' CAISSONS 11-5' PORCH CAISSONS EXHIBIT DIVISION |
|
| 11/15/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 25 REBAR GAGES OK |
|
| 11/02/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) PARTIAL 2 CASSIONS AT EAST SIDE OF ELEPHANT BARN |
|
| 11/01/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 4 CASSIONS SOUTHEAST CORNER OF BARN 2) CURB AT SLIDE GATE |
|
| 10/28/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 5 CASSIONS SOUTH SIDE OF ELEPHANT BARN |
|
| 10/21/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 9 CASSIONS ON EAST SIDE OF ELEPHANT BARN |
|
| 10/20/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* | |
| 10/19/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 7 CAISSIONS AT NORTH EAST CORNERS OF ELEPHANT BARN |
|
| 10/03/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 11 AT CAISSION COLUMN FOOTINGS (CAGES) 1) STEM WALL (STEEL BOLLARD CURB) DEAIL #7 PAGE 2S-301 AT ERD BLDG OK TO POUR PROGRESS AREAS |
|
| 09/28/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) ERD CURBS AS MARKED ON PLAN |
|
| 09/21/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 28 CASSIONS OK RECALL WHEN SET 2) EAST SHOT CRETE SCREEN WALL FOOTINGS COMPLETE |
|
| 09/15/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) EAST TERMINATE MOUND FOOTING AND STAIRS AT KOPJE |
|
| 09/12/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) FOOTING FOR WEST TERMINATE MOUND STRUCTURE REINFORCEMENT STEEL OK PER RFI-30D DETAIL 29A |
|
| 07/29/2011 | EXCAVATION/LAYOUT REBAR & ZON | Cancelled | IVRS - RI canceled | |
| 07/29/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | ||
| 07/22/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) CMU FOOTINGS AT COPJE 2) CURBS FOR BEDROOM 2 AND COMMUNITY ROOM |
|
| 07/21/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) MISSING REBAR AND OVER SPACED |
|
| 07/19/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) ERD GRADE BEAMS 2) LAST EDR CASSION |
|
| 07/18/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* | |
| 07/14/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* NEEDS CORNER ? AND ENGINEER OK ON 3 PC STIRRUP NOT HOOKED TOP TO BOTTOM |
|
| 07/13/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) ELEPHANT POOL COMPLETE |
|
| 07/12/2011 | EXCAVATION/LAYOUT REBAR & ZON | Cancelled | IVRS - RI canceled | |
| 07/08/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) PLANTER FOOTING, 1 CAISSON AT ERD CENTER |
|
| 07/07/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) POOL COMPLETE |
|
| 07/06/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 3 CAISSONS EAST SIDE OF ERD |
|
| 06/29/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 5 CASSIONS RECALL WHEN SET 2) NEED RFI THAT UNTREATED PLYWOOD BOX INSTEAD OF BACK FILL IS OK 3) IF POURED SOLID OK TO POUR WITH SPECIAL INSPECTION |
|
| 06/27/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) RINO MOAT FOOTING-CONFOMATEC INSPECTED |
|
| 06/24/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) CAISSONS TO HAVE #12 VERT AND ALTERNATE STIRRUP HOOKS |
|
| 06/20/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) 2 PONY WALL FOOTING SOUTHWEST SIDE OF ELEPHANT BARN |
|
| 06/16/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) PONY WALL FOOTING AT MOAT, CMU WALL AT LIFT STATION |
|
| 06/06/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* MUDWALLS | |
| 05/26/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) WALL "A"-8' 10" ; WALL "B" AT 12'-16'' WALL "C" 16'-20' OK TO GROUT PROGRESS AREAS |
|
| 05/19/2011 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* | |
| 05/13/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) COPJA PLANTER FOOTING |
|
| 05/09/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) FOOT REINF. FOR 8" CMU SCREEN WALL AT LSS BLDG AND AT ELEPHANT POOL-SPECIAL INSPECTED CONFORMATECH |
|
| 05/06/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) SCREEN WALL FOOTING AT LSS TANK OK TO POUR FOOTING |
|
| 05/03/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* ROACK FOOTING AT SLIDE GATE SPECIAL INSPECTED | |
| 05/02/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* FINAL SE SHOTCRETE FOOTING WE CORNER ROCK AND SHOTCRETE |
|
| 04/25/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* | |
| 04/21/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) TRAINING BARN COMPLETE EXCEPT POP OUTS |
|
| 04/20/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) EAST OF LSS 11' CMU WALL FOOTING 2) ELEPHANT BARN: NO PIPE TO RUN THRU FOOTING (8) OS-301 NOT READY TO POUR |
|
| 04/14/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* | |
| 04/12/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) PARTIAL FOOTING ALONG 22ND ST FROM 174' TO APPROX 219'-SPECIAL INSPECTED |
|
| 04/11/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* REINFORCEMENT STEEL FOR FOUNDATION OF SHOT CRETE RETAINING WALL FROM 135' TO 189' FROM STARTING POINT - OK - SPECIAL BY CONFORMATECH | |
| 04/05/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :*REINFORCING STEEL @ SHOTCRETE DEEPEND FOOTING AT UTILITIES (HIGH PRESURE SEWER LINE @ SOUTH OF SITE) APPROX 25 L.F. IN LENGTH - FOOTING SECTION A5 50' OR 65' EAST OFSTARING POINT. SPECIAL INSPECTION BY CONTRACTOR | |
| 04/04/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* | |
| 03/24/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) MOAT FOOTING COMPLETE |
|
| 03/16/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) SHOT CRETE WALL FOOTING AT SOUTH EAST CORNER OF EXHIBIT "B" AT NORTH END-SHOT CRETE WALL IN SOUTH EAST CORNER APPROX SOUTH 60 L.F. FROM NORTH END OF WALL AT SOUTH WEST COTRNER OF EXHIBIT "A" FROM 0 TO 4' THE PERIMETER AFTER CMU WALL-SPECIAL BY CONFORMATECH |
|
| 03/14/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) MOAT FOOTING COMPLETE |
|
| 03/09/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) EAST SHOT CUTE WALL 65' FROM SOUTH EAST CORNER |
|
| 02/23/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) SHOT CRETE WALL FOOTING FOR SITE WALL FROM WEST END TO 140 L.F. EAST-OK 2) SPECIAL INSPECTION BY CONFORMATECH |
|
| 02/17/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* | |
| 02/10/2011 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* |