Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T10CM00607

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/26/2010 FRAMING Approved IVRS - Inspection :*
1) GARAGE ROOF LPI 32 PLUS INSTALLED, PLAN CALLS FOR T.J.I. 360
2) I DON'T HAVE LPI BOOK, I DON'T KNOW WHAT SIZE TOP/BOTTOM CORDS ARE TO HAVE CHANGE ON PLAN OR LPI
05/20/2010 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LEAVE T.J.I. SPECS FOR GARAGE ROOF PLAN CALLS FOR 14" T.J.I. (360'S), YOU INSTALLED (L.P.I. 32 PLUS)
2) REPLACE FIRE/BLK AT DRYER DUCT
3) REINFORCE DIVERTER STUD, MASTER SHOWER
4) MISSING CUT NAILS, MSTR CLOSET-MARKED ON FLOOR
5) SHEARWALL #2 GARAGE WALL, NEED BLOCKED OSB BEHIND DROP SOFFIT UP TO T/PLATE ALL EDGES BLOCKED
6) MISSING 1/2" DIAMETER BOLTS #5 SHEARWALL B-PLATE GARAGE 32" ON CENTER
7) BANG PLATE ROMEX S. KIT WALL
8) MOVE RECEPT AWAY FROM MASTER TUB VERT. LINE (TUB BOUNDRY)
9) LOOSE BOT. PLATE S. BEDROOM DOORS (MARKED ON FLOOR)
10) #3 SHEARWALL AT BED #3 PLATE BOLTS 60" ON CENTER