| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2010 | FIRE - FINAL | Approved | PER INSP CARD | |
| 04/09/2010 | FIRE - FINAL | Denied | 1. Exit sign in server room hallway shuts off when circuit breaker is opened. 2. Emergency egress lighting not working. 3. Repair exit sign at West end office. |
|
| 03/23/2010 | FIRE - FINAL | Denied | 1. Check on sprinkler coverage in hall and fix pipe hanger in N/W side of of warehouse. 2. Replace key locks on doors in warehouse (North side). All egress doors shall operate with one simple motion and no special knowledge. 3. Service/maintain exit signs. 4. Emergency egress lighting is required. 5.All doors leading to an exit must operate with one simple motion and no special knowledge (west side office area). |