Permit: T09PL02108

Parcel: 112052790

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/31/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/24/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CALLED 325-8681 THIS CONTRACTOR STATES HE IS NOT CONTRACTOR OF RECORD. CORRECT THIS AT 201 N. STONE
2) NO ACCESS AT 9:07 AM NO TEST IN PLACE
3) PAY REINSPECTION FEE AT 201 N STONE FOR NON COMPLIANCE WITH CORRECTIONS FROM 12/17/09
12/17/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST TO HAVE MINIMUM 10 PSI AND HOLD PRESSURE FOR 15 MINUTES
2) PROVIDE RIDGID PIPING THRU PARTITION TO VALVE FOR STOVE AT STOVE AREA ( FLEX CANNOT PENETRATE THRU WALL OR PARTITION)
3) PROVIDE BONDING OF BLDG GAS PIPING SYSTEM