Permit: T09OT02840

Parcel: 11704141A


Addresses:

601 N STONE AV

Inspection Status: Denied

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/20/2010 FIRE - FINAL Denied Not approved 1/20/10
1.) Need accurate and approved floor plans. (Sales area and 2nd. floor area)
2.) Need address numbers for the building. Must be readily visible from the street fronting the building.
3.) Need a thumb-turn lock for the 2nd door, (sales area)
4.) Need sign over main door, sales area, that reads, "DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED".
3.) Replace broken glass, sales area.
4.) Cover openings in walls and ceiling.
a.) ceiling tiles
b.) damaged sheet rock
c.) closet near bathroom
5.) Sign over door leading into the warehouse/storage area reading, "NOT AN EXIT".
6.) Fire rated door seperating the non-sprinklered Sales Area and the Warehouse must remain closed at all times.
7.) Replace the keyed lock with a thumb-turn lock on the
exterior double-doors located north of the three rool-up doors.
8.) Portable extinghuishers need annual inspection and servicing.
9.) Replace all missing cover plates.
10.) West bay. secure open end wiring.
11.) Limit accumulation of storage material in warehouse area.
12.) All storage material must be orderly and must not obstruct or impede the exit pathway.
13.) Need directional exit signs in the warehous and shop area.
14.) Need cover plates for open j-boxes 3rd level.
15.) Need cover for ballast light.
16.) Provide "NO SMOKING " SIGNS in the shop area.
17.) HOT WORKS area must be clear of comustibles during operations or welding shield must be provided.
18.) Need a portable fire extinguished when doing Hot Work.
19.) SW door in the shop area needs a sign reading, NOT AN EXIT, on the inside and DOOR BLOCKED,(4-6 inche letters) on the out side.
20.) Need the updated annual sprinkler report.
21.) Need the updated 5 year check valve inspection report.
22.) Need to secure the butterfly valve on the sprinkler riser (chain)
23.) All exits must have a clear and unobstructed path.
24.) Need breaker blanks for the two electrical panels.
25.) Replace the painted sprinkler heads located in small storage room.
26.) The exit door at the end of the stair way is hard to open. Must be readily openable.