Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - LIFE SAFETY
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2009 | INSP - LIFE SAFETY | Correction Required | EXIT light not illuminated above basement door. - Repair the EXIT lighting unit. Iinternational FIre Code (IFC) 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. |