Case: T09FR03758

Parcel: 11720007A


Addresses:

255 W ALAMEDA ST

Inspection Status: Correction Required

Inspection History: INSP - LIFE SAFETY

Date Description Inspector Results Comments
12/10/2009 INSP - LIFE SAFETY Correction Required EXIT light not illuminated above basement door.
- Repair the EXIT lighting unit.
Iinternational FIre Code (IFC) 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment or an on-site generator.