Case: T09FR03758
Case Details
Entered Date:
12/14/2009
Applicant:
CITY OF TUCSON
Description:
MAITS - FIRE CODE COMPLIANCE INSPECTION
Outstanding Inspections
Case Number: T09FR03758
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 12/10/2009 | INSP - LIFE SAFETY | RHEATH | Correction Required | EXIT light not illuminated above basement door. - Repair the EXIT lighting unit. Iinternational FIre Code (IFC) 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. |
| 12/10/2009 | VIOL - FIRE PROTECTION SYSTEMS | RHEATH | Correction Required | An escutcheon plate is falling away from the sprinkler in the Money room on the first floor. - Re-align the escutcheon plate IFC Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. |
| 12/14/2009 | VIOL - HAZARDOUS MATERIALS,GEN | RHEATH | Correction Required | Gallon cans of old paint and a Bromine bucket are stored in an electrical closet. Old electrical equipment is stored in an HVAC Ventilation Area. - Remove items and discard. IFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. |