Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
12/08/2009 | INSP - FULL | Violation | 1.) TFC 605.6 INSTALL COVER PLATE ON JUNCTION BOX IN CEILING OF MECHANICAL ROOM ON 2ND FLOOR. | |
12/08/2009 | INSP - FULL | Violation | 2.) TFC 703.1.1 SEAL HOLE (3"X6") IN CEILING OF BEAUTY SALON BACKROOM. | |
12/08/2009 | INSP - FULL | Violation | 3.) TFC 1008.1.8 REPLACE DOUBLE KEYED DEAD BOLT ON KITCHEN NORTH EXIT DOOR WITH A THUMB TURN LATCH. | |
12/08/2009 | INSP - FULL | Violation | 4.) TFC 1008.1.8 REMOVE SLIDE BOLT LATCH AND REPLACE DOUBLE KEYED DEAD BOLT WITH A THUMB TURN LATCH ON NORTH EXIT DOOR FROM LAUNDRY ROOM. | |
12/08/2009 | INSP - FULL | Violation | 5.) TFC 605.6 THE ELECTRICAL WIRE SPLICE IN TELEPHONE ROOM MUST BE ENCLOSED IN AN APPROVED JUNCTION BOX. | |
12/08/2009 | INSP - FULL | Violation | 6.) TFC 901.6.2 FIRE ALARM ANNUAL INSP. REPORT MUST BE SUBMITTED. | |
12/08/2009 | INSP - FULL | Approved | NOTE: SPRINKLER SYSTEM ANNUAL INSP. REPORT WAS SUBMITTED TO TIME OF INSP. FIRE DRILL RECORDS ARE IN COMPLIANCE. |