Case: T09FR03696

Parcel: 13325182A


Addresses:

8468 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/23/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 5 YEAR CHECK VALVE INSP WAS DONE AND GAUGES WERE REPLACED. APPROVED.
12/07/2009 INSP - FULL Violation 1.) TFC 605.4 REPLACE MULTI-PLUG ADAPTER WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION BY COFFEE MACHINE IN DINING ROOM.
12/07/2009 INSP - FULL Violation 2.) TFC 1006.3 EMERGENCY ILLUMINATION UNITS ARE NOT WORKING IN THE FOLLOWING LOCATIONS:
a.) IN MECHANICAL ROOM BY KITCHEN.
b.) IN HALLWAY BY ROOM # 604.
12/07/2009 INSP - FULL Violation 3.) TFC 605.4 INSTALL COVER PLATE ON OUTLET IN MECHANICAL ROOM BY KITCHEN.
12/07/2009 INSP - FULL Violation 4.) TFC 703.1.1 SEAL WALL PENETRATION IN HALLWAY ACROSS FROM ROOM # 805.
12/07/2009 INSP - FULL Violation 5.) TFC 1011.4 REPAIR EMERGENCY ILLUMINATION UNIT BY LAUNDRY. INTERNALLY ILLUMINATED EXIT SIGN IS NOT ILLUMINATED.
12/07/2009 INSP - FULL Violation 6.) TFC 605.6 ENCLOSE WIRE SPLICES IN RISER ROOM IN AN APPROVED JUNCTION BOX.
12/07/2009 INSP - FULL Violation 7.) TFC 901.6 CHECK VALVE ON RISER IS DUE FOR 5 YEAR INTERNAL INSPECTION.
12/07/2009 INSP - FULL Violation 8.) TFC 901.6 GUAGES ON RISER ARE DUE FOR 5 YEAR REPLACEMENT.