Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 5 YEAR CHECK VALVE INSP WAS DONE AND GAUGES WERE REPLACED. APPROVED. | |
| 12/07/2009 | INSP - FULL | Violation | 1.) TFC 605.4 REPLACE MULTI-PLUG ADAPTER WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION BY COFFEE MACHINE IN DINING ROOM. | |
| 12/07/2009 | INSP - FULL | Violation | 2.) TFC 1006.3 EMERGENCY ILLUMINATION UNITS ARE NOT WORKING IN THE FOLLOWING LOCATIONS: a.) IN MECHANICAL ROOM BY KITCHEN. b.) IN HALLWAY BY ROOM # 604. |
|
| 12/07/2009 | INSP - FULL | Violation | 3.) TFC 605.4 INSTALL COVER PLATE ON OUTLET IN MECHANICAL ROOM BY KITCHEN. | |
| 12/07/2009 | INSP - FULL | Violation | 4.) TFC 703.1.1 SEAL WALL PENETRATION IN HALLWAY ACROSS FROM ROOM # 805. | |
| 12/07/2009 | INSP - FULL | Violation | 5.) TFC 1011.4 REPAIR EMERGENCY ILLUMINATION UNIT BY LAUNDRY. INTERNALLY ILLUMINATED EXIT SIGN IS NOT ILLUMINATED. | |
| 12/07/2009 | INSP - FULL | Violation | 6.) TFC 605.6 ENCLOSE WIRE SPLICES IN RISER ROOM IN AN APPROVED JUNCTION BOX. | |
| 12/07/2009 | INSP - FULL | Violation | 7.) TFC 901.6 CHECK VALVE ON RISER IS DUE FOR 5 YEAR INTERNAL INSPECTION. | |
| 12/07/2009 | INSP - FULL | Violation | 8.) TFC 901.6 GUAGES ON RISER ARE DUE FOR 5 YEAR REPLACEMENT. |