Case: T09FR03696
Case Details
Entered Date:
12/07/2009
Applicant:
ALS WEST INC DBA: AHC WEST INC
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03696
Case Description: INSPECTION
Total Completed Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 8.) TFC 901.6 GUAGES ON RISER ARE DUE FOR 5 YEAR REPLACEMENT. |
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 7.) TFC 901.6 CHECK VALVE ON RISER IS DUE FOR 5 YEAR INTERNAL INSPECTION. |
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 6.) TFC 605.6 ENCLOSE WIRE SPLICES IN RISER ROOM IN AN APPROVED JUNCTION BOX. |
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 5.) TFC 1011.4 REPAIR EMERGENCY ILLUMINATION UNIT BY LAUNDRY. INTERNALLY ILLUMINATED EXIT SIGN IS NOT ILLUMINATED. |
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 4.) TFC 703.1.1 SEAL WALL PENETRATION IN HALLWAY ACROSS FROM ROOM # 805. |
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 3.) TFC 605.4 INSTALL COVER PLATE ON OUTLET IN MECHANICAL ROOM BY KITCHEN. |
| 12/07/2009 | INSP - FULL | RSPANGLE | Approved | 2.) TFC 1006.3 EMERGENCY ILLUMINATION UNITS ARE NOT WORKING IN THE FOLLOWING LOCATIONS: a.) IN MECHANICAL ROOM BY KITCHEN. b.) IN HALLWAY BY ROOM # 604. |