Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ALL VIOLATIONS ABATED | |
| 11/30/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC Section 904.11.7 All deep-fat fryers shall be installed with at least a 16 inch (406 mm) space between the fryer and surface flames of adjacent cooking appliances. Exception: 1. Where a steel or tempered glass baffle plate is installed at a minimum 8 inches (203 mm) in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking appliance are at different horizontal planes, the minimum height of 8 inches (203 mm) shall be measured from the higher of the two. _____ 1. THE FRYER SHALL COMPLY WITH THE ABOVE REQUIREMENTS. |
|
| 11/30/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. NOZZLES NEED TO BE ADJUSTED FOR PROPER COVERAGE ON HOOD SYSTEM. _____2. NEED SIX MONTH ANUAL HOOD INSPECTION DONE. SHOW REPORT UPON REINSPECTION. |
|
| 11/30/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____1. CLASS K EXTINGUISHER IN KITCHENT NEEDS TO BE SERVICED AND TAGED. |
|
| 11/30/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 901.4.1 Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. ____1. SPRINKLER SYSTEM SHALL BE SERVICED PROVIDE REPORT UPON REINSPECTION. |