Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09FR03666

Parcel: 11205283F


Addresses:

2990 N CAMPBELL AV

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/25/2010 VIOL - FIRE PROTECTION SYSTEMS Approved ALL VIOLATIONS ABATED
11/30/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC Section 904.11.7 All deep-fat fryers shall be installed with at least a 16 inch (406 mm)
space between the fryer and surface flames of adjacent cooking appliances.

Exception:
1. Where a steel or tempered glass baffle plate is installed at a minimum 8 inches
(203 mm) in height between the fryer and surface flames of the adjacent cooking
appliance, the requirement for a 16 inch space shall not apply. Where the fryer
and the surface flames of the adjacent cooking appliance are at different
horizontal planes, the minimum height of 8 inches (203 mm) shall be measured
from the higher of the two.

_____ 1. THE FRYER SHALL COMPLY WITH THE ABOVE REQUIREMENTS.
11/30/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

_____1. NOZZLES NEED TO BE ADJUSTED FOR PROPER COVERAGE ON HOOD SYSTEM.
_____2. NEED SIX MONTH ANUAL HOOD INSPECTION DONE. SHOW REPORT UPON REINSPECTION.
11/30/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____1. CLASS K EXTINGUISHER IN KITCHENT NEEDS TO BE SERVICED AND TAGED.
11/30/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.4.1 Required fire protection systems. Fire protection
systems required by this code or the International Building
Code shall be installed, repaired, operated, tested and maintained
in accordance with this code.


____1. SPRINKLER SYSTEM SHALL BE SERVICED PROVIDE REPORT UPON REINSPECTION.