Case: T09FR03567

Parcel: 12404032C


Addresses:

1423 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
01/07/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
11/16/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Fire alarm is due for annual inspection/service. Repair any deficiencies noted in report. Provide a copy of the report.
____Provide a copy of the report from the sprinkler system annual inspection/service. Make sure all deficiencies have been corrected.
____Complete the smoke detector log provided. Provide during reinspection.
11/16/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.

____Class K extinguisher in kitchen must be mounted. Make sure it is mounted within 30ft. of the cooking equipment.
11/16/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____Service and tag exinguisher in kitchen. Class K.