Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 11/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Fire alarm is due for annual inspection/service. Repair any deficiencies noted in report. Provide a copy of the report. ____Provide a copy of the report from the sprinkler system annual inspection/service. Make sure all deficiencies have been corrected. ____Complete the smoke detector log provided. Provide during reinspection. |
|
| 11/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. ____Class K extinguisher in kitchen must be mounted. Make sure it is mounted within 30ft. of the cooking equipment. |
|
| 11/16/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Service and tag exinguisher in kitchen. Class K. |