Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/16/2009

Applicant:

ARIZONA BOARD OF REGENTS

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03567
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
11/16/2009 VIOL - BUILDING SVCS & SYSTEMS JVINCENT Approved [M] 609.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of the International Mechanical Code. [M] 609.2 Where required.AType I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. ____The stove/oven in the "warming kitchen" will require a Type I hood system since it is a communal appliance and considered to be for commercial purposes.
11/16/2009 VIOL - MEANS OF EGRESS JVINCENT Approved 1027.3 Exit sign illumination. ____Repair exit sign in foyer and chapter room.
11/16/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Service and tag exinguisher in kitchen. Class K.
11/16/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. ____Class K extinguisher in kitchen must be mounted. Make sure it is mounted within 30ft. of the cooking equipment.
11/16/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Approved 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Fire alarm is due for annual inspection/service. Repair any deficiencies noted in report. Provide a copy of the report. ____Provide a copy of the report from the sprinkler system annual inspection/service. Make sure all deficiencies have been corrected. ____Complete the smoke detector log provided. Provide during reinspection.
11/16/2009 INSP - FULL JVINCENT Approved FULL FIRE INSPECTION.