Case: T09FR03466

Parcel: 124040760


Addresses:

1509 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
01/28/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Complete smoke detector log and provide during reinspection. Every bedroom and room used for sleeping purposes requires a smoke detector.
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.2.7 Group R. Existing sorority and fraternity house shall have automatic sprinkler systems installed by October 22, 2010 and permits by October 22, 2009.

____You have until December 3, 2009 to obtain pemits. You are also being issued a PRECITATION with this report for not obtaining permits. It is possible a CITATION will be issued if you do not comply.
11/04/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.1 General. Automatic fire-extinguishing systems, other
than automatic sprinkler systems, shall be designed, installed,
inspected, tested and maintained in accordance with the provisions
of this section and the applicable referenced standards.
904.5 Wet-chemical systems. Wet-chemical extinguishing
systems shall be installed, maintained, periodically inspected
and tested in accordance with NFPA 17A and their listing.

____Repair any deficiencies listed in your hood system annual inspection report.
____ All six burners do not seem to have proper coverage. Make sure your report states you have proper coverage.
____The portable deep fat fryer is not placed under a nozzle. Last year you were also ordered to move it under a nozzle to provide proper coverage. You complied but it has since been moved again. If this continues you will be issued a citation.