Case: T09FR03446

Parcel: 12404032B


Addresses:

1443 E 1ST ST

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
11/03/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 903.4 Sprinkler system monitoring and alarms. All valves
controlling the water supply for automatic sprinkler systems,
pumps, tanks, water levels and temperatures, critical air pressures,
andwater-flowswitches on all sprinkler systems shall be
electrically supervised OR LOCKED IN THE OPEN POSITION.

____Lock the control valve in the open position.