Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised OR LOCKED IN THE OPEN POSITION. ____Lock the control valve in the open position. |