Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

11/03/2009

Applicant:

DELTA GAMMA HOUSE CORPORATION OF ALPHA

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR03446
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
11/03/2009 INSP - FULL JVINCENT Violation FULL FIRE INSPECTION.
11/03/2009 VIOL - ADMINISTRATION JVINCENT Violation 107.2.1 Test and inspection records. Required test and inspection records shall be available to the fire code official at all times or such records as the fire code official designates shall be filed with the fire code official. ____Provide annual inspection reports for Fire Sprinkler System and Fire Alarm. Make sure all deficiencies have been corrected.
11/03/2009 VIOL - FIRE PROTECTION SYSTEMS JVINCENT Violation 903.4 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, andwater-flowswitches on all sprinkler systems shall be electrically supervised OR LOCKED IN THE OPEN POSITION. ____Lock the control valve in the open position.
11/03/2009 VIOL - MEANS OF EGRESS JVINCENT Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____Remove keyed locks from sunroof door and sunroof security gate. Replace with thumbturn locks.
11/03/2009 VIOL - MEANS OF EGRESS JVINCENT Violation 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. 1027.5 Illumination emergency power. 1027.4 Power source. ____Repair emergency lighting unit and exit sign in chapter room. ____Repair emergency lighting units in south hallway 2nd floor.