Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09FR03406

Parcel: 117031840


Addresses:

740 N MAIN AV

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
10/29/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1004.3 Posting of occupant load. Every room or space that is
an assembly occupancy shall have the occupant load of the
room or space posted in a conspicuous place, near the main exit
or exit access doorway from the room or space. Posted signs
shall be of an approved legible permanent design and shall be
maintained by the owner or authorized agent.

_____1. Post the occupant load on the wall by the main entrance.
10/29/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure, an emergency electrical
system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and
spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings
required to have two or more exits.
3. Exterior egress components at other than the level of exit
discharge until exit discharge is accomplished for buildings
required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section
1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for
exit discharge doorways in buildings required to have
two or more exits.
The emergency power system shall provide power for a
duration of not less than 90 minutes and shall consist of storage
batteries, unit equipment or an on-site generator. The installation
of the emergency power system shall be in accordance
with Section 2702 of the International Building Code.

_____1. Emergency lighting units shall be installed to automatically illuminate the exit, exit access and exit discharge in the event of power supply failure.
10/29/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1011.1 Where required. Exits and exit access doors shall be
marked by an approved exit sign readily visible from any direction
of egress travel. Access to exits shall be marked by readily
visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. Exit sign
placement shall be such that no point in a corridor is more than
100 feet (30 480 mm)or the listed viewing distance for the sign,
whichever is less, from the nearest visible exit sign.

_____1. Install internally illuminated EXIT signs above the exit doors.
10/29/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.9 Panic and fire exit hardware. Where panic and
fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall
extend at least one-half of the door leaf width.
2. The maximum unlatching force shall not exceed 15
pounds (67 N).
Each door in a means of egress from a GroupAor E occupancy
having an occupant load of 50 or more and any Group
H occupancy shall not be provided with a latch or lock
unless it is panic hardware or fire exit hardware.
Exception:Amain exit of a Group Aoccupancy in compliance
with Section 1008.1.8.3, Item 2.
Electrical rooms with equipment rated 1,200 amperes or
more and over 6 feet (1829 mm) wide that contain
overcurrent devices, switching devices or control devices
with exit access doors must be equipped with panic hardware
and doors must swing in the direction of egress.
If balanced doors are used and panic hardware is
required, the panic hardware shall be the push-pad type and
the pad shall not extend more then one-half the width of the
door measured from the latch side.

_____1. Panic Hardware shall be installed on the exit doors.