Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/29/2009

Applicant:

LEAL STEVEN

Description:

Full Fire Prevention Inspection. Douglas Vento

Outstanding Inspections

Case Number: T09FR03406
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
10/29/2009 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. _____1. Address numbers shall comply with Pima County address display requirements. NOTE: See attached requirements.
10/29/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage from obstructing the electrical panel.
10/29/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove all extension cords used for permanent wiring. NOTE: Replace them with fused multi-plug adapters. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
10/29/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Properly cover the open spaces in the electrical panel.
10/29/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. _____1. Post the occupant load on the wall by the main entrance.
10/29/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. _____1. Emergency lighting units shall be installed to automatically illuminate the exit, exit access and exit discharge in the event of power supply failure.
10/29/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception:Amain exit of a Group Aoccupancy in compliance with Section 1008.1.8.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide that contain overcurrent devices, switching devices or control devices with exit access doors must be equipped with panic hardware and doors must swing in the direction of egress. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more then one-half the width of the door measured from the latch side. _____1. Panic Hardware shall be installed on the exit doors.
10/29/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm)or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. _____1. Install internally illuminated EXIT signs above the exit doors.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03406
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/29/2009 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code vilations. NOTE:Your building has been referred to the Housing and Community Development department for operating without a C of O.