Case: T09FR03400

Parcel: 124040110


Addresses:

1435 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
01/13/2010 VIOL - MEANS OF EGRESS Approved
10/28/2009 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:
1. Group A having 50 or more occupants.

____Add one emergency lighting unit to the Chapter room. This room becomes an Assembly type occupancy during meetings with 50 or more occupants.
10/28/2009 VIOL - MEANS OF EGRESS Violation 1026.1 General. In addition to the means of egress required by
this chapter, provisions shall be made for emergency escape
and rescue in Group R and I-1 occupancies.
Exceptions:
1. In other than Group R-3 occupancies, buildings
equipped throughout with an approved automatic
sprinkler system in accordance with Section
903.3.1.1 or 903.3.1.2.

____This is for your reference. The bedroom in room/casita #27 no longer has windows. This is OK since the building has an approved automatic sprinkler system (see Exception).
10/28/2009 VIOL - MEANS OF EGRESS Violation 1026.4 Operational constraints. Emergency escape and rescue
openings shall be operational from the inside of the room
without the use of keys or tools. Bars, grilles, grates or similar
devices are permitted to be placed over emergency escape and
rescue openings provided the minimum net clear opening size
complies with Section 1026.2 and such devices shall be
releasable or removable from the inside without the use of a
key, tool or force greater than that which is required for normal
operation of the escape and rescue opening. Where such bars,
grilles, grates or similar devices are installed in existing buildings,
smoke alarms shall be installed in accordance with Sections
907.2.10 regardless of the valuation of the alteration.

____Bedroom in Casita #28 has a window with security bars mounted on the exterior. The bars do not have an emergency release. Either replace the bars with ones that have an emergency release or remove them.