Case: T09FR03400
Case Details
Entered Date:
10/28/2009
Applicant:
GAMMA ZETA BLDG ASSN
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR03400
Case Description: INSPECTION
Total Completed Inspections - 6
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1026.4 Operational constraints. Emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are permitted to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with Section 1026.2 and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the escape and rescue opening. Where such bars, grilles, grates or similar devices are installed in existing buildings, smoke alarms shall be installed in accordance with Sections 907.2.10 regardless of the valuation of the alteration. ____Bedroom in Casita #28 has a window with security bars mounted on the exterior. The bars do not have an emergency release. Either replace the bars with ones that have an emergency release or remove them. |
| 10/28/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1026.1 General. In addition to the means of egress required by this chapter, provisions shall be made for emergency escape and rescue in Group R and I-1 occupancies. Exceptions: 1. In other than Group R-3 occupancies, buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. ____This is for your reference. The bedroom in room/casita #27 no longer has windows. This is OK since the building has an approved automatic sprinkler system (see Exception). |
| 10/28/2009 | VIOL - ADMINISTRATION | JVINCENT | Approved | 107.2.1 Test and inspection records. Required test and inspection records shall be available to the fire code official at all times or such records as the fire code official designates shall be filed with the fire code official. ____Provide a copy of the annual fire sprinkler inspection report. |
| 10/28/2009 | VIOL - MEANS OF EGRESS | JVINCENT | Approved | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: 1. Group A having 50 or more occupants. ____Add one emergency lighting unit to the Chapter room. This room becomes an Assembly type occupancy during meetings with 50 or more occupants. |
| 10/28/2009 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Approved | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____Trim vegetation around Fire Dept. Connections. |
| 10/28/2009 | INSP - FULL | JVINCENT | Approved |