Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T09FR03230
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 1. An extention cord with a multiple adapter is providing power to 2 power strips. Remove the extention cord and connect the power strips directly to an outlet. INTERNATIONAL FIRE CODE (IFC) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords shall be used only with portable appliances. 2. A sandard 2 prong receptacle is installed in the bathroom. Replace the standard receptacle with a ground-fault ciruit-interrupter (GFI). National Electric Code Standard 70, 210.8. requires a GFI in all bathrooms. |