Case: T09FR03230

Parcel: 12407211B


Addresses:

930 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/08/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 1. An extention cord with a multiple adapter is providing power to 2 power strips. Remove the extention cord and connect the power strips directly to an outlet. INTERNATIONAL FIRE CODE (IFC) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords shall be used only with portable appliances.
2. A sandard 2 prong receptacle is installed in the bathroom. Replace the standard receptacle with a ground-fault ciruit-interrupter (GFI). National Electric Code Standard 70, 210.8. requires a GFI in all bathrooms.