Description:

FIRE CODE COMPLIANCE INSPECTION

Outstanding Inspections

Case Number: T09FR03230
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
10/08/2009 VIOL - BUILDING SVCS & SYSTEMS RHEATH Correction Required 1. An extention cord with a multiple adapter is providing power to 2 power strips. Remove the extention cord and connect the power strips directly to an outlet. INTERNATIONAL FIRE CODE (IFC) 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords shall be used only with portable appliances. 2. A sandard 2 prong receptacle is installed in the bathroom. Replace the standard receptacle with a ground-fault ciruit-interrupter (GFI). National Electric Code Standard 70, 210.8. requires a GFI in all bathrooms.
10/08/2009 VIOL - FIRE PROTECTION SYSTEMS RHEATH Correction Required 1. A Fire Extinguisher is not available within the occupancy. Install a 10 LB ABC extinguisher. IFC 906.5 Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. A Re-Inspection will be conducted on 10/27/2009. ______________________ R. HEATH, INSPECTOR __________________________ PROPERTY REPRESENTATIVE
10/13/2009 INSP - FULL RHEATH Correction Required