Case: T09FR02536

Parcel: 11504602D


Addresses:

865 E UNIVERSITY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR02536

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/30/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CCORRECTED WITHIN 30 DAYS A COPY OF THE REPAIR REPORT SHALL BE SENT TO THIS OFFICE

1) GENTLE BENS - ALCOVE BY THE NEW COOLER IS REQUIRED TO BE SPRINKLERED. CHECK THE COOLER FOR SPRINKLER INSTALLATION, INTERIOR.

2) FRONT WEST ALCOVE - A SPRINKLER HEAD IS LOCATED TO HIGH IN HARD LID CEILING

3) PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE REPLACED OR CALIBRATED

4) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE