Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR02536
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CCORRECTED WITHIN 30 DAYS A COPY OF THE REPAIR REPORT SHALL BE SENT TO THIS OFFICE 1) GENTLE BENS - ALCOVE BY THE NEW COOLER IS REQUIRED TO BE SPRINKLERED. CHECK THE COOLER FOR SPRINKLER INSTALLATION, INTERIOR. 2) FRONT WEST ALCOVE - A SPRINKLER HEAD IS LOCATED TO HIGH IN HARD LID CEILING 3) PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE REPLACED OR CALIBRATED 4) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE |