Case: T09FR02535

Parcel: 12405007B


Addresses:

845 E UNIVERSITY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR02535

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/30/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE REPAIRED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE

1) SPRING NAIL SALON - THE PAINTED QUICK RESPONSE SPRINKLER HEAD IN THE STORE ROOM SHALL BE REPLACED

2) PEI WEI - ALL RECESSED SPRINKLER HEADS SHALL HAVE THE MISSING RECESSED STYLE ESCUTCHEONS MISSING SHALL HAVE THEM REPLACED

3) PITA PIT - RECESSED SPRINKLER HEAD ESCUTCHEONS THAT ARE MISSING SHALL BE REPLACED ( 2 PLACES)

4) PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE REPLACED OR CALIBRATED

5) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE