Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

07/30/2009

Applicant:

WEST MAIN GATE CENTER LLC

Description:

SPRINKLER COMPLAINT

Outstanding Inspections

Case Number: T09FR02535
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
07/30/2009 INSP - FULL EDESCHAI Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE REPAIRED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE 1) SPRING NAIL SALON - THE PAINTED QUICK RESPONSE SPRINKLER HEAD IN THE STORE ROOM SHALL BE REPLACED 2) PEI WEI - ALL RECESSED SPRINKLER HEADS SHALL HAVE THE MISSING RECESSED STYLE ESCUTCHEONS MISSING SHALL HAVE THEM REPLACED 3) PITA PIT - RECESSED SPRINKLER HEAD ESCUTCHEONS THAT ARE MISSING SHALL BE REPLACED ( 2 PLACES) 4) PRESSURE GUAGES ARE 5 YEARS OLD AND SHALL BE REPLACED OR CALIBRATED 5) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE