Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - SELF INSPECTION PROGRAM
Case Number - T09FR02507
Inspection Description - INSP - SELF INSPECTION PROGRAM
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2009 | INSP - SELF INSPECTION PROGRAM | Correction Required | " 1IFC 901.6: If you have a fire extinguisher in your building, has it been serviced within the past 12 months? Fire extinguishers shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. |
|
07/29/2009 | INSP - SELF INSPECTION PROGRAM | Correction Required | 2. IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. |