Inspection History Details
Inspection Status: Continued
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2009 | VIOL - BUILDING SVCS & SYSTEMS | Continued | All items not corrected: the sprinkler was serviced and 5 year valve inspection performed; some extension cords are still being used. Once sprinkler report is received, I will re-inspect. | |
| 07/22/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | Unfused multiple outlets and extension cords are used throughout the plant. Discontinue using these devices. IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. 605.4.1 Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. 605.4.3 Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 605.5.1 Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. Please have all discrepancies corrected by 8/20/2009 for scheduled re-inspection. Contact me at 791-4014 if you have any questions. ROBERT HEATH, INSPECTOR TUCSON FIRE PREVENTION DIVISION PROPERTY REPRESENTATIVE |