Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR02045
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) A SPRINKLER HEAD EXCEEDS THE DISTANCE OFF A WALL. IT IS NOW 9' AND THE ALLOWABLE DISTANCE IS 7' 6" |