Case: T09FR02045

Parcel: 13312006M

Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR02045

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/24/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) A SPRINKLER HEAD EXCEEDS THE DISTANCE OFF A WALL. IT IS NOW 9' AND THE ALLOWABLE DISTANCE IS 7' 6"