Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

06/24/2009

Applicant:

248 S OCCIDENTAL BOULEVARD DE LLC 34.88% &

Description:

SPRINKLER COMPLAINT

Outstanding Inspections

Case Number: T09FR02045
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
06/24/2009 INSP - FULL EDESCHAI Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) A SPRINKLER HEAD EXCEEDS THE DISTANCE OFF A WALL. IT IS NOW 9' AND THE ALLOWABLE DISTANCE IS 7' 6"