Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2009 | INSP - FULL | Approved | CONTRACTORS REPORT TO SYSTEMS DEAR KATRINA, BE ADVISED THAT AS YOUR REQUEST, FORWARDED IS THE APPROVED COPY, THAT SPRINKLER DEFICIENCIES HAVE BEEN CORRECTED, SO THAT YOU MAY PROCEED WITH OBTAINING A CERTIFICATE OF OCCUPANCY. |
|
| 06/10/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE 1) PROVIDE THE RECESSED ESCUTCHEON ASSEMBLY IN THE BASEMENT HALL 2) PRESSURE GUAGES ARE OVER 5 YEARS OLD, TO BE REPLACED OR RECALIBRATED |