Case: T09FR01916

Parcel: 12009317B


Addresses:

4625 S 3RD AV

Inspection Status: Violation

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
06/10/2009 VIOL - PRECAUTION AGAINST FIRE Violation 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger.
06/10/2009 VIOL - PRECAUTION AGAINST FIRE Violation 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.