Description:

Synergy installations fire inspection.

Outstanding Inspections

Case Number: T09FR01916
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
06/10/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 309.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 906 having a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger.
06/10/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
06/10/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
06/10/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
06/10/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
06/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
06/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
06/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. __Provide copy of last sprinkler inspection report.
06/10/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.
06/10/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way.
06/10/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ___Provide illuminated exit sign for door going from warehouse into front office.
06/10/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches. Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width. ____Create and maintain aisles in warehouse and storage area.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR01916
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/10/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 791-4502 ext. 146, Fax 791-5346.
06/24/2009 INSP - REINSPECTION JLOYA Approved All violations abated.