Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2009 | VIOL - MEANS OF EGRESS | Correction Required | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the the front rest room door, as bolt lock of any kind are not permitted 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ The secondary locking device shall be disabled or replaced to meet code standards. I.E. the lock shall release when twisted from the interior side on the doors located in the Kitchens rear exit door and in the 4 & 5 yr old room. 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Always maintain a clear path for your outside gates as they are in the egress path to a place of refuge. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo) |