Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR01874
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2009 | INSP - FULL | Approved | Annual MAITS Inspection of TPDHQ had the following violations. Sec.# 311.2.3 Place signage on the mobile shelving stating: "At the end of the day - shelving must be placed 18" apart", or similar. Sec. # 315.2.3Remove combustible materials from Mechanical room on 2nd Floor Storage behind door# 2254A. Sec.# 605.1 Cover exposed electrical box in Records Area. Cover exposed, energized electrical box in Old Evidence Area behind door # 3328B. All deficiencies corrected by 22-Apr. |