Case: T09FR01693

Parcel: 125120810


Addresses:

3330 E SPEEDWAY BL

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/18/2009 INSP - FULL Correction Required ADDENDUM:
1) ITEM # 1 SHALL BE ADRESSED BY APPEAL TO THE FIRE CODE OFFICIAL

2) ITEM # 2 SHALL BE ADRESSED AT THIS TIME FOR REPAIRS

3) ALL STORAGE SHALL BE REMOVED TO REDUCE A FIRE LOAD

2) ITEM # 2
05/14/2009 INSP - FULL Correction Required DURING THE LAST FIRE PROTECTION INSPECTION THE
FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) THERE ARE 139, FIFTY YEAR OLD SPRINKLERS IN SERVICE. THEY ARE REQUIRED TO BE CHANGED OUT OR A SAMPLE FROM ONE OR MORE AREAS SHALL BE TESTED

2) PRESSURE GUAGES AT THE RISER SHALL BE RECALIBRATED OR CHANGED OUT