Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR01691

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/14/2009 INSP - FULL Correction Required DURING THE LAST FIRE PROTECTION INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND AHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) THERE ARE 95, FIFTY YEAR OLD SPRINKLERS IN SERVICE. THEY ARE REQUIRED TO BE CHANGED OUT OR A SAMPLE FROM ONE OR MORE AREAS SHALL BE TESTED.

2) PRESSURE GUAGES AT THE RISER SHALL BE RECALIBRATED OR CHANGED OUT. ACCORDING TO THE REPORT THEY ARE OUT DATED.

3) THE WATER MOTOR GONG IS IN OPERATIVE AND SHALL BE IN REPAIR