Inspection Status: Violation
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/06/2009 |
INSP - FULL |
|
Violation |
1.) TFC 605.5 THE EXTENSION CORD IN BENEFITS OFFICE MUST BE REMOVED. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
2.) TFC 605.4.2 THE RELOCATABLE POWER STRIPS IN NURSE MELI'S OFFICE CANNOT BE CONNECTED IN SERIES. EACH POWER STRIP MUST BE PLUGGED DIRECTLY INTO AN OUTLET. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
3.) TFC 605.6 THE ELECTRICAL JUNCTION BOXES IN CEILING OF I.S. DEPT. MUST HAVE COVER PLATES INSTALLED. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
4.) TFC 605.6 THE ELECTRICAL OUTLET IN BAPTISMAL NEWORK CLOSET MUST HAVE A COVER PLATE INSTALLED. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
5.) TFC 315.2.4 THE COMBUSTIBLE STORAGE UNDER STAIRS IN STAIRWELL CLOSET IS NOT PERMITTED UNLESS THIS AREA HAS 1 HR. RATED CONSTRUCTION MATERIALS. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
6.) TFC 605.4 THE MULTI-PLUG ADAPTER IN KIM SCHULTZ'S OFFICE MUST BE REMOVED. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
7.) TFC 901.6.2 THE FIRE ALARM SYSTEM MUST BE INSPECTED ANNUALLY AND A REPORT ON FILE AT TIME OF FIRE PREVENTION INSPECTION. |
| 05/06/2009 |
INSP - FULL |
|
Violation |
8.) TFC 703.1.1 IN NUMEROUS LOCATIONS IN THE BAPTISMAL AREA HOLES IN THE SHEETROCK OF THE WALLS AND CEILING MUST BE REPAIRED. ALSO IN NETWORK CLOSET. |