FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR01558
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
05/06/2009 INSP - FULL RSPANGLE Violation 1.) TFC 605.5 THE EXTENSION CORD IN BENEFITS OFFICE MUST BE REMOVED.
05/06/2009 INSP - FULL RSPANGLE Violation 2.) TFC 605.4.2 THE RELOCATABLE POWER STRIPS IN NURSE MELI'S OFFICE CANNOT BE CONNECTED IN SERIES. EACH POWER STRIP MUST BE PLUGGED DIRECTLY INTO AN OUTLET.
05/06/2009 INSP - FULL RSPANGLE Violation 3.) TFC 605.6 THE ELECTRICAL JUNCTION BOXES IN CEILING OF I.S. DEPT. MUST HAVE COVER PLATES INSTALLED.
05/06/2009 INSP - FULL RSPANGLE Violation 4.) TFC 605.6 THE ELECTRICAL OUTLET IN BAPTISMAL NEWORK CLOSET MUST HAVE A COVER PLATE INSTALLED.
05/06/2009 INSP - FULL RSPANGLE Violation 5.) TFC 315.2.4 THE COMBUSTIBLE STORAGE UNDER STAIRS IN STAIRWELL CLOSET IS NOT PERMITTED UNLESS THIS AREA HAS 1 HR. RATED CONSTRUCTION MATERIALS.
05/06/2009 INSP - FULL RSPANGLE Violation 6.) TFC 605.4 THE MULTI-PLUG ADAPTER IN KIM SCHULTZ'S OFFICE MUST BE REMOVED.
05/06/2009 INSP - FULL RSPANGLE Violation 7.) TFC 901.6.2 THE FIRE ALARM SYSTEM MUST BE INSPECTED ANNUALLY AND A REPORT ON FILE AT TIME OF FIRE PREVENTION INSPECTION.
05/06/2009 INSP - FULL RSPANGLE Violation 8.) TFC 703.1.1 IN NUMEROUS LOCATIONS IN THE BAPTISMAL AREA HOLES IN THE SHEETROCK OF THE WALLS AND CEILING MUST BE REPAIRED. ALSO IN NETWORK CLOSET.