Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR01516

Parcel: 141148150


Addresses:

9040 E VALENCIA RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01516

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2009 INSP - FULL Approved On 6/18/09 I investigated a complaint that generated from the hood system inspection report from the inspection I had required this business to have. The report stated that there was no K class extinguisher and insufficient coverage for two burners. I set a deadline for today to have the K class extinguisher for his restaurant, and approval of the burner by hood system contractor before the burners could be used. The burners were arranged so that coverage is sufficient per the report given by Sun Devil/Wildcat.
05/26/2009 INSP - FULL Violation New problem: open face plate where Exit sign used to be.
Needs K class extinguisher per the company who inspected the hood and a 2 b range has no coverage.
05/01/2009 INSP - FULL Violation The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Wiring through drop ceiling above S and N entrance, over fishtank, in kitchen, behind reception counter in Sushi diner, to coffee pot on South wall, behind toaster oven in salad bar.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact.
REQUIRED CORRECTION: Plug all appliances and signs into a wall socket or power strip. Cannot extend electrical plug through drop ceiling.

___2. PROBLEM: Two multiplug adapters in wall outlets over N and S entrance, 1 yellow three prong adapter and cord attached to soda machine in Sushi side of Restaurant.
TFD REFERENCE: 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
REQUIRED CORRECTION: Remove all unapproved adapters.

___3. PROBLEM: Loose CO2 cylinders in hall near bathrooms.
TFC REFERENCE:3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
REQUIRED CORRECTION: Secure your tanks with chain or bungee to a sturdy object or the wall.

___4. PROBLEM: Fire extinguishers in kitchen have not been serviced in the past year.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or removed.
REQUIRED CORRECTION: Have portable fire extinguishers serviced by a qualified individual.

___5. PROBLEM: Electric panel in hall is blocked.

TFD REFERENCE: IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
REQUIRED CORRECTION: You will provide a clear space around your electric panels.

___6. PROBLEM: Storage in washing machine closet is too close to the sprinkler head.
TFC REFERENCE: 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
REQUIRED CORRECTION: You will provide 18 inches clearance between storage and below sprinkler heads.

___7. PROBLEM: Your hood system is overdue for inspection.
TFC REFERENCE: IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.

___8. PROBLEM: There is not an exit sign over the required exit from the dining hall in Kyo Sushi.
TFC REFERENCE: IFC IFC 1011.1 Access to required exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants.
REQUIRED CORRECTION: You will place an exit sign over your South most exit in the Kyo Sushi portion of the Restaurant.

___8. PROBLEM: Your emergency lighting on your exit signs is not working ( over main exits, NW Hallway exit )
TFC REFERENCE: IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: You will cause all of your emergency lighting to operate properly.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

__X_Approved

___Not Approved