Case: T09FR01343

Parcel: 125010490


Addresses:

2635 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01343

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2009 INSP - FULL Approved all items abated
04/20/2009 INSP - FULL Correction Required FIRE INSPECTION REPORT
T09FR01343
04/20/2009

Bruce's Lock Shop
ATTN: Bruce Fairchild
2635 E. Broadway Bl.
Tucson, AZ. 85716



Mr. Fairchild

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on April 20, 2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with local modifications). A Re-inspection will be performed on or about May 4, 2009.



Notice of Violations:

_____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact…
" SW corner of the showroom
" Door leading to the backroom
" Clock above the front desk
" Main office

_____ 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
" Tammy's office

605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
" Ceiling in the showroom
" Backroom where the wall was removed
" Kitchen: j-box and romex
" J-box must be secured in Tammy's office
605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
" Shop West wall

703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
" Ceiling and walls in the shop area

1008.1.8 Locks.
Exit doors shall be operable from the egress side without use of a key, special knowledge of effort.
" Rear door (2639)
" Rear door (2635)

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical.
" Check all exits signs for compliance

304.1.2 Overgrown Vegetation.
Overgrown vegetation shall be cut and removed near the rear of the property.


The Tucson Fire Department is committed to the protection of your property. Your help as a business owner and as a citizen is greatly appreciated.

__________________________________________________
Property owner or Property Representative Signature
_________________________________
Abatement Date
__________________________
Captain Signature



Sincerely,


Jimmy R. Davis, Jr
Fire Inspector
Tucson Fire Department