Inspection Status: Violation
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2009 |
INSP - FULL |
|
Violation |
1.) TFC 906.7 THE PORTABLE FIRE EXTINGUISHER IN FRONT OFFICE MUST BE MOUNTED ON WALL BRACKET. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
2.) TFC 901.6 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN THE KITCHEN BY THE ICE MACHINE MUST BE SEALED. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
3.) TFC 901.6 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN THE KITCHEN STORAGE ROOM MUST BE SEALED. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
4.) TFC 901.6 TWO SPRINKLER HEADS HAVE A GAP AT THE CEILING IN THE POOL ROOM THAT MUST BE SEALED. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
5.) TFC 605.4 THE MULIT-PLUG ELECTRICAL ADAPTER IN THE HAIR SALON NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
6.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT BY ROOM #217 NEEDS TO BE SERVICED/REPAIRED TO ILLUMINATE PRORERLY. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
7.) TFC 605.6 THE FLUORESCENT LIGHT FIXTURE IN THE 2ND FLOOR D-WING STORAGE ROOM NEEDS A COVER PLATE TO ENCLOSE OPEN WIRE SPLICES. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
8.) TFC 703.1.1 THE WALL PENETRATION BEHIND THE DOOR IN THE 2ND FLOOR D-WING REFUSE CLOSET MUST BE SEALED. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
9.) TFC 906.1 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEONS IN SHOP MUST BE SEALED. |
| 03/09/2009 |
INSP - FULL |
|
Violation |
10.) TFC 906.1 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN 3RD FLOOR STORGE ROOM BY "C" ELEVATOR NEEDS TO BE SEALED. |