Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

03/09/2009

Applicant:

ATRIA CAMPANA DEL RIO LLC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR00837
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
03/09/2009 INSP - FULL RSPANGLE Violation 1.) TFC 906.7 THE PORTABLE FIRE EXTINGUISHER IN FRONT OFFICE MUST BE MOUNTED ON WALL BRACKET.
03/09/2009 INSP - FULL RSPANGLE Violation 10.) TFC 906.1 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN 3RD FLOOR STORGE ROOM BY "C" ELEVATOR NEEDS TO BE SEALED.
03/09/2009 INSP - FULL RSPANGLE Violation 2.) TFC 901.6 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN THE KITCHEN BY THE ICE MACHINE MUST BE SEALED.
03/09/2009 INSP - FULL RSPANGLE Violation 3.) TFC 901.6 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEON IN THE KITCHEN STORAGE ROOM MUST BE SEALED.
03/09/2009 INSP - FULL RSPANGLE Violation 4.) TFC 901.6 TWO SPRINKLER HEADS HAVE A GAP AT THE CEILING IN THE POOL ROOM THAT MUST BE SEALED.
03/09/2009 INSP - FULL RSPANGLE Violation 5.) TFC 605.4 THE MULIT-PLUG ELECTRICAL ADAPTER IN THE HAIR SALON NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION.
03/09/2009 INSP - FULL RSPANGLE Violation 6.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT BY ROOM #217 NEEDS TO BE SERVICED/REPAIRED TO ILLUMINATE PRORERLY.
03/09/2009 INSP - FULL RSPANGLE Violation 7.) TFC 605.6 THE FLUORESCENT LIGHT FIXTURE IN THE 2ND FLOOR D-WING STORAGE ROOM NEEDS A COVER PLATE TO ENCLOSE OPEN WIRE SPLICES.
03/09/2009 INSP - FULL RSPANGLE Violation 8.) TFC 703.1.1 THE WALL PENETRATION BEHIND THE DOOR IN THE 2ND FLOOR D-WING REFUSE CLOSET MUST BE SEALED.
03/09/2009 INSP - FULL RSPANGLE Violation 9.) TFC 906.1 THE GAP ABOVE THE SPRINKLER HEAD ESCUTCHEONS IN SHOP MUST BE SEALED.