Case: T09FR00829

Parcel: 13322500G


Addresses:

7155 E BROADWAY BL

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
03/06/2009 VIOL - MEANS OF EGRESS Violation 504.2 Maintenance of exterior doors and openings.
Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED.

***To ensure that there is no confusion on the required exiting from the building the following must be completed

A sign stating "NOT AN EXIT" affixed to the interior side of the door. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door.

Fire marshal allowing exit configuration because of the small public showroom and the majority of store is employees only***

____ Place the proper signage as stated above

1027.3 Exit sign illumination.
Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose.

_____ Fix, repair, and/or replace all exit signs in order to meet code standards.

________________________________________________
(Michael Pursley, Inspector, Tucson Fire Department)