| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2009 | INSP - FULL | Correction Required | PRE-CITATION DELEATED. SPRINKLER REPORT RECEIVED WITH THE FOLLOWING DEFICIENCIES: 1) PROVIDE A HYDRAULIC CALCULATION PLATE AT THE RISER IF NOT A PIPE SCHEDULED SYSTEM 2) SPRINKLER HEADS SHALL NOR EXCEED THE ALLOWABLE DISTENCE OFF WALLS 3) CONTROL VALVES SHALL BE SECURED WITH A LOCK AND CHAIN 4) THERE SHALL NOT BE A MIXTURE OF DIFFERENT SPRINKLER CLASSIFICATIONS IN THE CLASSROOM 5) A 5 YEAR INTERNAL VALVE INSPECTION SHALL BE PERFORMED IF THE TIME FRAME INDICATES PLEASE FORWARD WITHIN 30 DAYS A REPORT OF COMPLETION OF DEFICIENCIES. |
|
| 04/20/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 2-24-09, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 902 N. STONE. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT |
|
| 02/24/2009 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS |