Case: T09FR00748

Parcel: 117022090


Addresses:

902 N STONE AV

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/18/2009 INSP - FULL Correction Required PRE-CITATION DELEATED. SPRINKLER REPORT RECEIVED WITH THE FOLLOWING DEFICIENCIES:

1) PROVIDE A HYDRAULIC CALCULATION PLATE AT THE RISER IF NOT A PIPE SCHEDULED SYSTEM

2) SPRINKLER HEADS SHALL NOR EXCEED THE ALLOWABLE DISTENCE OFF WALLS

3) CONTROL VALVES SHALL BE SECURED WITH A LOCK AND CHAIN

4) THERE SHALL NOT BE A MIXTURE OF DIFFERENT SPRINKLER CLASSIFICATIONS IN THE CLASSROOM

5) A 5 YEAR INTERNAL VALVE INSPECTION SHALL BE PERFORMED IF THE TIME FRAME INDICATES

PLEASE FORWARD WITHIN 30 DAYS A REPORT OF COMPLETION OF DEFICIENCIES.
04/20/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 2-24-09, FOR THE ABOVE LISTED DEFICIENCY CONCERNING THE FIRE PROTECTION SYSTEM AT 902 N. STONE. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT
02/24/2009 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED ON AN ANNUAL BASIS