Case: T09FR00748
Case Details
Entered Date:
02/24/2009
Applicant:
ARIZONA BANK
Description:
SPRINKLER INSPECTION
Outstanding Inspections
Case Number: T09FR00748
Case Status: FIELD
Case Description: COMPLAINT (RESIDENTIAL)
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2009 | INSP - FULL | EDESCHAI | Correction Required | PRE-CITATION DELEATED. SPRINKLER REPORT RECEIVED WITH THE FOLLOWING DEFICIENCIES: 1) PROVIDE A HYDRAULIC CALCULATION PLATE AT THE RISER IF NOT A PIPE SCHEDULED SYSTEM 2) SPRINKLER HEADS SHALL NOR EXCEED THE ALLOWABLE DISTENCE OFF WALLS 3) CONTROL VALVES SHALL BE SECURED WITH A LOCK AND CHAIN 4) THERE SHALL NOT BE A MIXTURE OF DIFFERENT SPRINKLER CLASSIFICATIONS IN THE CLASSROOM 5) A 5 YEAR INTERNAL VALVE INSPECTION SHALL BE PERFORMED IF THE TIME FRAME INDICATES PLEASE FORWARD WITHIN 30 DAYS A REPORT OF COMPLETION OF DEFICIENCIES. |