Case: T09FR00632

Parcel: 10602262A


Addresses:

3602 N ORACLE RD


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T09FR00632

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
03/25/2009 VIOL - MOTOR FUEL DISPENSING Approved Reports recieved
02/18/2009 VIOL - MOTOR FUEL DISPENSING Correction Required Devices used for final testing shall be capable of detecting leaks as small as 0.05 gallon per hour. Leaking piping and equipment shall not be used until repaired or replaced. The fire code official is authorized to require that the test be conducted in the code official's presence.

" Please provide a copy of either the tank tightness and line leak test results or if a automatic tank gauge system is used please provide the annual calibration test report for that device and the print out showing that the system has passed its leak test.

2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

" Please provide test results.
02/18/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

" Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.